Skip to main content

Purpose of Boiler Water Tests

Purpose of boiler water treatment

  • Prevent corrosion of boiler tubes and shell
  • Prevent scale formation and hence maintain heat transfer rates.
  • Control sludge formation within the boiler.
  • Control foaming and priming. Prevent entry of foreign matter, oil etc. into the boiler via feed system
  • Extend boiler survey to the maximum allowed.


FOLLOWING TESTS ARE CARRIED OUT:-

Boiler water tests are therefore done to ensure that the chemical levels are maintained as required.

Chlorides : This is a measure of presence of Chlorides, usually an indication of contamination of Boiler water with sea water.( Sodium Chloride / Calcium or Magnesium Chloride ) . This results in increased scale formation, acidity and boiler priming. 

Normal levels: Chlorides< 300 ppm. 

What to do if chloride content increases beyond normal value.?

Check for leakages of SW into the system, mainly from atmospheric condenser leak and rectify any leaks found. Blowdown at regular and frequent intervals and replenish with distilled water till chloride content becomes normal.


Alkalinity:- There are two measurements of Alkalinity


P Alkalinity – It measures Alkalinity due to Hydroxides and Phosphates. pH testing also determines Alkalinity but is less accurate method. If Alkalinity is too low than corrosion could occur. Too high Alkalinity may result in Foaming.

TOTAL ALKALINITY – It measures the Alkalinity of all the other boiler salts, including bicarbonates. Total Alkalinity should be less than 2x P Alkalinity. This may occur when large quantities of untreated feed is admitted in to the boiler.

pH: 9.8-10.2




Phosphates- A sufficient reserve of Phosphates should be present
in Boiler Water, to neutralize any Hardness salts. These salts would
deposit as scale on the heating surfaces if the phosphate reserves
are too low while too high reserves of phosphates may lead to foaming and excess production of sludge which if not removed, will deposit on heating surfaces

Normal Values of Phosphate: 15 – 25 ppm

Oxygen Scavengers:- These chemicals are added to chemically
deoxygenate the boiler water. Useful in closed feed system as the oxygen will enter the boiler water in open hot well. The test is carried out to find the levels of chemical reserve of Hydrazine used for the purpose of deoxygenating the boiler water. If the Chemical reserve is low, corrosion will occur, if the hydrazine level is high it will form ammonia which can attack copper alloys in the feed system

Normal values of Hydrazine: 0.05-0.1 ppm

TOTAL DISSOLVED SOLIDS:- This is a measure of all the dissolved solids in the boiler water including those from the chemicals added. This test is done by using a electrical conductivity meter but the sample should be neutralized before test as the alkaline sample will affect the TDS reading

Comments

Popular posts from this blog

Difference Between A, B & C-Class Divisions?

IMO Symbol A Class Division  IMO Symbol B Class Division  SOLAS has tables for structural fire protection requirement of bulkheads and decks. The requirements depend on the spaces in question and are different for passenger ships and cargo ships. The Administration has required a test of a prototype bulkhead or deck in accordance with the Fire Test Procedures Code to ensure that it meets the above requirements for integrity and temperature rise. Types of Divisions: "A" Class "B" Class "C" Class "A" Class: "A" class divisions are those divisions formed by bulkheads and decks which comply with the following criteria: They are constructed of steel or equivalent material They are suitably stiffened They are constructed as to be capable of preventing the passage of smoke and flame to the end of the one-hour standard fire test. they are insulated with approved non-combustible materials such that the average tempera

Load Line & Why it is Important

Merchant ships have a marking on their hull know as the Plimsoll line or the Plimsoll mark, which indicates the limit until which ships can be loaded with enough cargo, internationally, the Plimsoll line on a ship is officially referred to as the international load line. Every type of ship has a different level of floating and the Plimsoll line on a ship generally varies from one vessel to another.  All vessels of 24 meters and more are required to have this Load line marking at the centre position of the length of summer load water line. There are two types of Load line markings:- Standard Load Line marking – This is applicable to all types of vessels. Timber Load Line Markings – This is applicable to vessels carrying timber cargo. These marks shall be punched on the surface of the hull making it visible even if the ship side paint fades out. The marks shall again be painted with white or yellow colour on a dark background/black on a light background.  The comp

Bilge Injection Valve

Bilge Injection is a valve that enables the engine room bilges to be pumped out directly overboard in the event of an emergency such as flooding. The valve is normally fitted to the end of a branch connection with the main sea water suction line. This enables large main seawater cooling pumps to be used as a bilge pump in an emergency. Emergencies like fire and flooding involve the use of seawater. If there is a fire, seawater is the biggest resource of water available in the sea. Similarly, if it involves flooding of the engine room, cargo spaces or any other place on the ship for that matter; you would again require pumping the sea water out of the ship. In both these cases, you require pumps.  There are two valves in close proximity namely main injection valve and bilge injection valve. Both of them have their own independent controls. The diameter of the bilge injection valve is kept nearly 66% of the main valve diameter which draws water directly from the sea through the